Current ratings are estimates calculated using the IEC 60287 method, not AS/NZS 3008 table values. Always confirm cable selection against AS/NZS 3008.1.1 and the Wiring Rules.
Voltage drop & cable size calculator
Enter the load, the run length and how the cable is installed. We'll show the smallest cable that passes on current rating and on voltage drop, then build the termination kit for it. Switch to DC for solar PV string and array cable or battery leads.
Result
Enter a load and a length to see the result.
All assumptions
Current ratings and correction factors calculated by East Coast Electrical Supplies with the IEC 60287 method from public physics; not AS/NZS 3008 table values.
- Ratings basis
- Estimates calculated with the IEC 60287 steady-state method (not AS/NZS 3008 table values)
- Air temperature (reference)
- 40 °C, still air, shaded (no sun)
- Ground temperature (reference)
- 25 °C
- Soil thermal resistivity
- 2.5 K·m/W (dry soil, allowing for drying out around the cable)
- Burial depth (reference)
- 0.5 m to the cable (or conduit) centre
- Maximum conductor temperature
- 90 °C XLPE (X-90), 75 °C PVC (V-75)
- Conductor
- Plain copper, ρ = 1.7241e-8 Ω·m at 20 °C, α = 0.00393/K. Stranded (class 2) × 1.13 for lay and area tolerance; flexible (class 5) a further × 1.05, and its rating × 0.97
- Frequency, losses
- 50 Hz; skin and proximity effect included; no dielectric, sheath or armour losses (LV, unarmoured)
- Thermal resistivity
- XLPE 3.5, PVC insulation 5, PVC fillers, sheath and conduit 6 K·m/W
- Cable dimensions
- Typical outside diameters from makers' datasheets (the Job Kit Builder data) where held, otherwise typical insulation and sheath thicknesses
- Three-phase circuits
- 3 loaded conductors (balanced, neutral not loaded); multicore = 4-core cable, single-core = 3 cables in trefoil
- Single-phase circuits
- 2 loaded conductors; multicore = 2C+E cable; single-core cables use the three-phase rating (safe side)
- Clipped / on tray (touching)
- The lower of clipped to a wall (75% of the surface sheds heat) and on a tray (85%)
- Small cables in conduit or insulation
- Ratings up to 16 mm² × 0.9 (conservative margin)
- Partly surrounded by thermal insulation
- Half the cable surface against insulation (treated as no heat flow)
- Spaced / on ladder
- One circuit: single layer, one cable diameter apart, free air. Two or more circuits: treated as touching or stacked (the touching grouping factor)
- Conduit
- Smallest PVC conduit with ≤ 40% fill, one circuit per conduit; in air, fixed to a wall
- Grouped circuits
- Identical, equally loaded circuits; in air bunched together (touching methods) or in a single layer (spaced); in the ground side by side, touching. The lowest factor across all sizes is used.
- Air and ground temperature factors
- √((θmax − θ) / (θmax − θref))
- Voltage drop
- Vd = k × I × L × (R cos φ + X sin φ), k = √3 three phase, 2 single phase; R at the maximum conductor temperature (safe side); reactance from cable geometry
DC mode (solar PV and battery cables)
- Ratings basis
- Estimates calculated with the IEC 60287 steady-state method (not AS/NZS 3008 or AS/NZS 5033 values)
- DC circuit
- 2 loaded single-core cables (positive and negative), each carrying the full current; touching, or one diameter apart on the spaced method
- Resistance
- d.c. only (no skin or proximity effect, no reactance). Fine stranded (class 5) copper: ρ/A × 1.1865; tinned (solar cable) a further × 1.03; at the maximum conductor temperature (safe side)
- Voltage drop
- Vd = 2 × I × L × R ÷ 1000 (R in Ω/km per conductor, L one way); % of the battery nominal voltage or the PV string's Vmp
- Solar PV current
- Cable rating checked at strings × Isc × the Isc factor (1.25 to start: sunlight above the 1000 W/m² test level); voltage drop worked at strings × Isc (above the working current Imp: safe side)
- Maximum conductor temperature
- 90 °C solar cable and XLPE / rubber, 75 °C PVC. Solar cable is often marked for 120 °C, but that is a limited-life rating, so 90 °C is used
- Solar cable
- Insulation and sheath 5 K·m/W (safe side for cross-linked compounds); wall 1.2 + 0.2 × √A mm (typical double insulation); rated 1.5 kV DC (general rating of the cable family)
- Battery cable dimensions
- Typical single-core flexible outside diameters from makers' datasheets (Job Kit Builder data) where held, otherwise typical insulation and sheath thicknesses
- Battery inverter cables
- At 60 V or less, the cable rating is checked at the DC current × 1.25 to allow for inverter ripple current (can be turned off). The voltage drop is worked at the DC current. Fuses, isolators, shunts and lug joints are not included in the drop
- Air temperature
- Reference 40 °C, shaded. Solar starts at 70 °C (under modules or on a roof). No allowance for direct sun on the cable: enter a higher temperature for cable in the sun
- Ground, soil, depth
- 25 °C ground, soil 2.5 K·m/W, 0.5 m deep
- Grouped circuits, conduit, small cables
- As for AC: the lowest factor across all sizes; one DC circuit per conduit; sizes up to 16 mm² in conduit or insulation × 0.9
- Not checked
- Fault current from batteries or PV, reverse current, string fusing, DC isolation, polarity, cable DC voltage rating (battery leads), connector ratings
A guide only. Current ratings are estimates calculated with the IEC 60287 method and voltage drop is calculated from cable resistance and reactance, for the method you pick. It doesn't check short-circuit, earth fault loop impedance or protective device coordination, or on DC: battery fault current, PV reverse current, string fusing, DC isolation or polarity. A licensed electrician must check every cable against AS/NZS 3000 and AS/NZS 3008.1.1 (and on DC, AS/NZS 5033 for solar and AS/NZS 5139 for batteries) before installing.
Disclaimer
This calculator is a guide only. Current ratings are estimates calculated using the IEC 60287 method and are not AS/NZS 3008.1.1 table values. Results depend on the information entered and the assumptions shown. Cable selection, voltage drop, protection and installation must be checked and confirmed by a licensed electrician or qualified electrical designer against AS/NZS 3000, AS/NZS 3008.1.1 and the manufacturer's data before use. This applies equally to DC, solar PV and battery cables: DC current ratings are also IEC 60287 method estimates, not AS/NZS 3008.1.1 or AS/NZS 5033 values, and DC designs must also be checked against AS/NZS 5033 (solar PV arrays), AS/NZS 5139 (battery systems) and the module, inverter, battery and cable makers' requirements, including the cable's DC voltage rating. East Coast Electrical Supplies accepts no responsibility for any loss, damage or injury arising from use of, or reliance on, these results.
© 2026 East Coast Electrical Supplies Pty Ltd. Calculator and page protected by copyright.
